This PoE power budget calculator adds up the power that Power over Ethernet devices need and compares it with a switch budget. It uses the IEEE 802.3af, 802.3at and 802.3bt classes with both the power the switch must provide (PSE) and the guaranteed power at the device (PD), shows cable loss, spare budget and headroom, and converts the load to BTU per hour.
Result
The result updates automatically as you change any input.
Formula and worked steps
Formulas used
- Port allocation = PSE power of the class: 4, 7, 15.4, 30, 45, 60, 75 or 90 W for classes 1 to 8 (class 0 = 15.4 W)
- Power at the device (PD) = PSE power minus worst-case cable loss at 100 m: 3.84, 6.49, 12.95, 25.5, 40, 51, 62 and 71.3 W
- Cable loss at a shorter length ~ (PSE - PD) x length / 100
- Budget check: sum of PSE allocations <= switch budget x (1 - headroom)
- BTU/h = watts x 3.412
- Switches usually reserve power by the class a device negotiates unless LLDP power negotiation lets them allocate what the device requests, so real consumption is often lower than the class total.
- Cable loss at shorter lengths is a linear approximation at constant current. Standards define the figures at 100 m with specified conductor resistance.
- Class lists follow IEEE 802.3af (classes 0 to 3), 802.3at (class 4) and 802.3bt (classes 5 to 8).
References
Sizing cooling for storage arrays and equipment? Use the storage power and cooling (BTU) calculator; this page converts only the PoE load into heat.
What is a PoE power budget?
Power over Ethernet delivers DC power over the same twisted pairs that carry data, so a phone, camera or wireless access point needs only one cable. The switch, called the power sourcing equipment (PSE), has a limited total PoE power budget set by its power supply. A 48-port switch may have 48 ports capable of 30 W each but a budget of only 740 W, so it can power about 24 devices of 30 W at once. The budget is the number that matters when you plan a closet, not the per-port rating.
Classes and standards
The devices a switch powers, the powered devices (PD), are grouped into classes. IEEE 802.3af (2003) defines classes 0 to 3, with up to 15.4 W at the port. 802.3at (2009), often called PoE+, adds class 4 at 30 W. 802.3bt (2018), sometimes called 4PPoE or PoE++, adds classes 5 to 8 with 45, 60, 75 and 90 W by using all four pairs. The PD figure is lower than the PSE figure because some power is lost in the cable: 12.95 W at the device for a 15.4 W port, 25.5 W for 30 W, 51 W for 60 W and 71.3 W for 90 W.
Allocation versus consumption
Most switches reserve power per port according to the class the device reports, so a class 4 access point holds 30 W in the budget even if it uses 12 W at the moment. Some devices and switches use LLDP to negotiate the actual need, which lets the switch reserve less. Reservation is the safe planning method, since devices can draw their class maximum at peak, for example when an access point enables all its radios or a camera turns on its heater and infrared lights.
How the PoE power budget calculator works
Formulas
Each line contains a device name, a quantity and either a class from 0 to 8 or the power the device needs, such as 20W. If you enter watts, the tool picks the smallest class whose PD power is at least that value, because the class defines what the device is guaranteed. The total PSE allocation is the sum of quantity times class PSE power. The result is compared with the switch budget less the headroom you want to keep free.
Worked example: 56 devices on a 1,440 W budget
24 access points of class 4 need 24 × 30 = 720 W. 12 cameras of class 3 need 12 × 15.4 = 184.8 W, and 20 phones of class 2 need 20 × 7 = 140 W. The total is 1,044.8 W, of which 897.2 W reaches the devices and 147.6 W is the worst-case cable loss. Against a 1,440 W budget the spare power is 395.2 W, 27.4%. With 20% headroom the usable budget is 1,152 W, so the design fits. If you want 40% headroom the usable budget is 864 W and the design no longer fits.
Cable loss and length
The standards guarantee the PD power at the maximum channel length of 100 m. For shorter runs the loss is lower, and the table shows an estimate that scales linearly. A class 4 device on a 50 m run could receive about 27.75 W rather than 25.5 W. This matters little for budgeting, since the switch reserves the PSE figure regardless, but it explains why short links have spare power.
Heat
All the power that leaves the switch ends up as heat, partly in the cable and partly in the devices. The calculator converts the PSE total to BTU per hour using 3.412 BTU per watt-hour: 1,044.8 W is about 3,565 BTU/h. This matters in a closet where the switch’s own heat adds to the load that the room must remove; for full facility planning use the storage power and cooling (BTU) calculator or the rack power calculator.
Why it matters for network engineers
PoE budget errors show up late, when a switch refuses to power the last access points or cameras or when a power supply fails and the closet loses PoE on the least important ports. A budget check at design time sets how many switches and what power supplies to buy. It also finds the effect of upgrades: moving from class 3 phones to class 4 access points or to 60 W devices can double the demand without any change in port count. Remember that the cable also limits PoE, since heat in a bundle raises temperature and attenuation; the cable length calculator covers derating.
Best practices and common mistakes
Keep 20% or more of the budget free for growth and for devices that draw more than expected. Use redundant power supplies sized so that the budget survives the loss of one, since many switches cut PoE first when a supply fails. Prefer Category 6A for high-power PoE, because larger conductors have less resistance and run cooler. Set priorities for critical ports, such as emergency phones and security cameras, so they stay powered when the budget is exhausted.
Common errors are adding up PD power instead of PSE power, forgetting that the switch’s data ports and PoE budget are different limits, and assuming that all devices draw the class maximum or none do. Another is using the nameplate watts of a device that really needs more when a heater or an extra radio is enabled. Do not forget that a class 4 device on an 802.3af port is simply not powered at full performance: confirm that the switch’s ports support the class you plan. For the load on the rest of the rack, the rack power calculator shows the electrical side.
Reading the table
The table lists each device group with its class, standard, PSE and PD power and the total reserved by the group. Use it as the closet’s power schedule: it shows which device groups dominate the budget, and which upgrades would change it the most. When a group dominates, consider alternatives such as a local power supply or a different device with a lower class.
FAQs
How much power does PoE+ provide?
802.3at (PoE+, class 4) provides 30 W at the switch port and a guaranteed 25.5 W at the device over a 100 m channel.
What is the difference between PSE and PD power?
PSE power is what the switch port supplies; PD power is what reaches the device after cable loss. For example 30 W at the PSE gives 25.5 W at the PD.
How do I calculate a switch PoE budget?
Add the PSE power of every powered device by class (or the power it negotiates) and compare the total with the switch PoE budget, leaving headroom for growth.
How much power does 802.3bt provide?
Type 3 (classes 5 and 6) provides 45 or 60 W and Type 4 (classes 7 and 8) provides 75 or 90 W at the port, using all four pairs.
Next, try the Ethernet cable maximum length, the rack power calculator and storage power and cooling calculator, or browse all Ethernet & Physical Layer calculators and the full list of network calculators.